ANALISA POMPA COOLING WATER SUPPLY UNTUK MENGHASILKAN STANDAR POMPA YANG EFISIEN DI COOLING TOWER 4 PT EFG

Authors

  • Yohanes Agung Purwoko Politeknik Astra
  • Fendi Ridho Febrianto
  • Ade Susilo
  • Rusdi Febriyanto

DOI:

https://doi.org/10.52453/t.v15i1.382

Keywords:

cooling tower, pump efficiency, pump standardization, energy.

Abstract

PT EFG Casting Plant is a manufacturing company that produces engine components used for Daihatsu car engines and some Toyota car engines. The production process is closely related to the high-temperature molding process using a casting machine. Overall, it is cooled using water from a cooling tower and the water is supplied using 2 pumps. An analysis was carried out which aims to determine the efficiency of the two cooling water supply pumps and from the results of this analysis obtained a low efficiency of 66% for each pump, this is because there is a 50% closure of the valve after the cooling water supply pump and if the valve is not done closing can cause cavitation in the pump. The low efficiency of the pump motor can result in less than optimal use of electric power in the pump. To overcome this problem the authors make improvements by providing standard pumps that have optimal efficiency in piping installations at PT EFG. So that from the results of these calculations it was found that initially using two cooling water supply pumps to meet the needs of cooling water, it can be reduced and replaced by using one efficient pump and power use can be optimized. Pump motor efficiency can increase up to 74% and can reduce the use of electric power by 53,049.9 kWh.

Keywords: cooling tower, pump efficiency, pump standardization, energy.

References

V. KUTIPAN DAN DAFTAR PUSTAKA

Sularso and H. Tahara. (2000). Pompa dan Kompresor. Jakarta: PT. Pradnya Paramita.

Ubaedilah. (2016). Analisis Kebutuhan Jenis dan Spesifikasi pompa untuk suplai air bersih Gedung Kantin Berlantai 3 PT Astra Daihatsu Motor. Jurnal Teknik Mesin (JTM): Vol. 05, No. 3.

Yopi Handoyo. (2015). Analisis Performa Cooling Tower LCT 400 Pada P.T. XYZ, Tambun Bekasi. Jurnal Imiah Teknik Mesin: Vol. 3, No.1.

Ziad Hafid Muhammad and Fajar Anggara. (2019). Analisa Head Pompa Water Intake Terhadap Self Cleaning Filter Pada PT XY. Jurnal Teknik Mesin: Vol. 08, No. 2.

Achmad Rijanto and Sueshti Rahayu Ningsih. (2022). Analisis Head Losses Pada Mesin Pompa Air Sawah. Majamecha: Vol. 4, No. 1.

E. P. Putro, E. Widodo, A. Fahruddin, and Iswanto. (2020). Perancangan Pompa Sentrifugal Dan Diameter Luar Impeller Untuk Kebutuhan Air Kapasitas 60 LPM Di Gedung F Dan C Universits Muhammadiyah Tangerang. Jurnal teknik: Vol. 7, No. 1.

Darianto. (2019). Analisa Pengaruh Waktu Dan Turbulensi Asap Pada Mesin Pengering Ikan Lele. JMEMME: Vol. 3, No. 2.

Fadhly Mujahid. (2021). Pengaruh Head Losses Mayor Dan Minor Pada Sistem Instalasi Turbin Pelton Skala Mikro. Jurnal Ilmiah Mahasiswa Teknik: Vol. 1 No. 4.

PT Lukes Indonesia. (2014). Ebara - Centrifugal End Suction Pump. 30 Maret 2023. 13.50 (Diakses 30 Maret 2023). Diakses dari https://www.lukesindonesia.com/ebara-centrifugal-end-suction-volute-pump/

PT Lukes Indonesia. (2014). Kurva Ebara Centrifugal End Suction – FSA. 30 Maret 2023. 14.55 (Diakses 30 Maret 2023). Diakses dari http://www.lukesindonesia.com/?s=Kurva+Ebara+Centrifugal+End+Suction+

Engineering Data Library (2020). Fluid Flow – General. 24 Maret 2023. 13.30 (Diakses 25 Maret 2023). Diakses dari https://edl.pumps.org/fluid-flow-iii/general.html

Hablinur Alkindi, Hasan Santosa, dan Edi Sutoyo. (2023). Analisa Head Losses Pada Circulating Flluida Air Dalam Dua Jenis Pipa. Jurnal Ilmiah Teknik Mesin: Vol. 9 No. 1.

Published

2024-06-26

How to Cite

Purwoko, Y. A., Ridho Febrianto, F., Susilo, A. ., & Febriyanto, R. (2024). ANALISA POMPA COOLING WATER SUPPLY UNTUK MENGHASILKAN STANDAR POMPA YANG EFISIEN DI COOLING TOWER 4 PT EFG. Technologic, 15(1). https://doi.org/10.52453/t.v15i1.382

Issue

Section

Table of Contents